Products
Building Material Power Tools Hand Tools Architectural Hardware Safety Products Electrical Products - Conduit Pipes - Cable Trunkings - Bends - Connector Bars - Single Core Cables - Auto Cables - Welding Cables - Telephone Cables - Fans - Two Core Cables - Coaxial Cables - Control Cables - Panel Wires (PVC Insulated Cables) - Screen Cables - LED Bulbs - LED Panel Lights - Tube Lights - Flood Lights - Residual Current Circuit Breakers - Miniature Circuit Breakers - Switch Disconnectors - Electric Isolaters - Circuit Breakers (Fixed Type) - Circuit Breakers (Adjustable Type) - Contactor - D Range - Overload Relay - D Range - LED Indicators - Push Buttons - Electric Mechanical Interlocks - Timer Switches - Power Energy Meters - Four Core Cables - Five Core Cabels Cast Iron Products Powertool Accessories Plumbing Products PVC Products Rubber Products Hardware Items Chemical Products Painting Products115A 59KW / 75HP 230V Schneider Contactor D Range
Rs. 117,950.00
ADD TO CARTModel No: LC1D115P7
Brand: Schneider
Call now
0774 953 653 | 0777 731 670 | 0771 200 201
Share
Brand - Schneider
Model - LC1D115P7
Range - TeSys
Range of Product - TeSys Deca
Product or Component Type - Contactor
Device short Name - LC1D
Contactor Application - Motor control
Resistive load
Utilisation category - AC-1
AC-4
AC-3
AC-3e
Poles Description - 3P
[Ue] Rated operational voltage - Power circuit: <= 1000 V AC 25...400 Hz
Power circuit: <= 300 V DC
[Ie] Rated operational current - 200 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
115 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
115 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] Control circuit voltage - 230 V AC 50/60 Hz
Complementary
Motor power kW - 30 kW at 220...230 V AC 50/60 Hz (AC-3)
55 kW at 380...400 V AC 50/60 Hz (AC-3)
59 kW at 415...440 V AC 50/60 Hz (AC-3)
75 kW at 500 V AC 50/60 Hz (AC-3)
80 kW at 660...690 V AC 50/60 Hz (AC-3)
65 kW at 1000 V AC 50/60 Hz (AC-3)
18.5 kW at 400 V AC 50/60 Hz (AC-4)
30 kW at 220...230 V AC 50/60 Hz (AC-3e)
55 kW at 380...400 V AC 50/60 Hz (AC-3e)
59 kW at 415...440 V AC 50/60 Hz (AC-3e)
75 kW at 500 V AC 50/60 Hz (AC-3e)
80 kW at 660...690 V AC 50/60 Hz (AC-3e)
65 kW at 1000 V AC 50/60 Hz (AC-3e)
Motor Power hp - 30 hp at 200/208 V AC 50/60 Hz for 3 phases motors
40 hp at 230/240 V AC 50/60 Hz for 3 phases motors
75 hp at 460/480 V AC 50/60 Hz for 3 phases motors
100 hp at 575/600 V AC 50/60 Hz for 3 phases motors
Compatibility code - LC1D
Pole contact composition - 3 NO
Protective cover - With
[Ith] conventional free air thermal current - 200 A (at 60 °C) for power circuit
Irms rated making capacity - 1260 A at 440 V for power circuit conforming to IEC 60947
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
Rated breaking capacity - 1100 A at 440 V for power circuit conforming to IEC 60947
[Icw] Rated short-time withstand current
250 A 40 °C - 10 min for power circuit
550 A 40 °C - 1 min for power circuit
950 A 40 °C - 10 s for power circuit
1100 A 40 °C - 1 s for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
Associated Fuse Rating - 250 A gG at <= 690 V coordination type 1 for power circuit
200 A gG at <= 690 V coordination type 2 for power circuit
10 A gG for signalling circuit
Average impedance - 0.6 mOhm - Ith 200 A 50 Hz for power circuit
Power dissipation per pole - 24 W AC-1
7.9 W AC-3
7.9 W AC-3e
[Ui] rated insulation voltage Power circuit - Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Power circuit: 1000 V conforming to IEC 60947-4-1
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
Overvoltage category - III
Pollution degree - 3
[Uimp] rated impulse withstand voltage - 8 kV conforming to IEC 60947
Safety reliability level - B10d = 684932 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 10000000 cycles contactor with mechanical load conforming to EN/ISO
13849-1
Mechanical durability - 8 Mcycles
Electrical durability - 0.8 Mcycles 200 A AC-1 at Ue <= 440 V
0.95 Mcycles 115 A AC-3 at Ue <= 440 V
0.95 Mcycles 115 A AC-3e at Ue <= 440 V
Control circuit type - AC at 50/60 Hz standard
Coil technology - Built-in bidirectional peak limiting diode suppressor
Control circuit voltage Limits - 0.3...0.5 Uc (-40…70 °C):drop-out AC 50/60 Hz
0.8...1.15 Uc (-40…55 °C):operational AC 50/60 Hz
1...1.15 Uc (55…70 °C):operational AC 50/60 Hz
Inrush Power in VA - 280…350 VA 60 Hz cos phi 0.8 (at 20 °C)
280…350 VA 50 Hz cos phi 0.8 (at 20 °C)
Hold-in power consumption in VA - 2…18 VA 60 Hz cos phi 0.3 (at 20 °C)
2…18 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat dissipation - 3…8 W at 50/60 Hz
Operating time - 6...20 ms opening
20...50 ms closing
Maximum operating rate - 2400 cyc/h 60 °C
Maximum operating rate - 2400 cyc/h at 60 °C
Mechanical robustness - Vibrations contactor open (2 Gn, 5...300 Hz)
Vibrations contactor closed (4 Gn, 5...300 Hz)
Shocks contactor closed (15 Gn for 11 ms)
Shocks contactor open (6 Gn for 11 ms)
Height - 158 mm
Width - 120 mm
Depth - 136 mm
Net weight - 2.5 kg
Packing Units
Unit Type of Package 1 - PCE
Number of Units in Package 1 - 1
Package 1 Height - 20.000 cm
Package 1 Width - 19.000 cm
Package 1 Length - 23.000 cm
Package 1 Weight - 2.480 kg
Unit Type of Package 2 - S06
Number of Units in Package 2 - 27
Package 2 Height - 75.000 cm
Package 2 Width - 60.000 cm
Package 2 Length - 80.000 cm
Package 2 Weight - 79.960 kg
18 Months Company Warranty