40A 18.5KW / 25HP 230V Schneider Contactor D Range

Product Photo

Rs. 41,940.00

ADD TO CART

Model No: LC1D40AP7

Brand: Schneider

 Schneider

Call now

0774 953 653 | 0777 731 670 | 0771 200 201

Share

             

Brand  - Schneider

Model - LC1D40AP7

Range - TeSys
TeSys Deca

Range of Product - TeSys Deca

Product or Component Type - Contactor

Device short Name - LC1D

Contactor Application - Motor control
Resistive load

Utilisation category -AC-4
AC-1
AC-3
AC-3e

Poles Description - 3P

[Ue] Rated operational voltage - Power circuit - 690 V AC 25...400 Hz
Power circuit <= 300 V DC

[Ie] Rated operational current - 60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
40 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
40 A (at <60 °C) at <= 440 V AC AC-3e for power circuit

[Uc] Control circuit voltage - 230 V AC 50/60 Hz

Complementary
Motor power kW - 18.5 kW at 380...400 V AC 50/60 Hz (AC-3)
11 kW at 220...230 V AC 50/60 Hz (AC-3)
22 kW at 415...440 V AC 50/60 Hz (AC-3)
22 kW at 500 V AC 50/60 Hz (AC-3)
30 kW at 660...690 V AC 50/60 Hz (AC-3)
9 kW at 400 V AC 50/60 Hz (AC-4)
18.5 kW at 380...400 V AC 50/60 Hz (AC-3e)
11 kW at 220...230 V AC 50/60 Hz (AC-3e)
22 kW at 415...440 V AC 50/60 Hz (AC-3e)
22 kW at 500 V AC 50/60 Hz (AC-3e)
30 kW at 660...690 V AC 50/60 Hz (AC-3e)

Motor Power hp - 5 hp at 230/240 V AC 50/60 Hz for 1 phase motors
10 hp at 230/240 V AC 50/60 Hz for 3 phases motors
30 hp at 575/600 V AC 50/60 Hz for 3 phases motors
10 hp at 200/208 V AC 50/60 Hz for 3 phases motors
3 hp at 115 V AC 50/60 Hz for 1 phase motors
30 hp at 460/480 V AC 50/60 Hz for 3 phases motors

Compatibility code - LC1D
Pole contact composition - 3 NO
Protective cover - With

[Ith] conventional free air thermal current - 10 A (at 60 °C) for signalling circuit
60 A (at 60 °C) for power circuit

Irms rated making capacity - 140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
800 A at 440 V for power circuit conforming to IEC 60947

Rated breaking capacity - 800 A at 440 V for power circuit conforming to IEC 60947

[Icw] Rated short-time withstand current

320 A 40 °C - 10 s for power circuit
720 A 40 °C - 1 s for power circuit
72 A 40 °C - 10 min for power circuit
165 A 40 °C - 1 min for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit

Associated Fuse Rating - 10 A gG for signalling circuit conforming to IEC 60947-5-1
80A gG at <= 690 V coordination type 1 for power circuit
80A gG at <= 690 V coordination type 2 for power circuit

Average impedance - 1.5 mOhm - Ith 50 A 50 Hz for power circuit

Power dissipation per pole - 2.4 W AC-3
5.4 W AC-1
2.4 W AC-3e

[Ui] rated insulation voltage Power circuit - 600 V CSA certified
Power circuit: 600 V UL certified
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
Power circuit: 690 V conforming to IEC 60947-4-1

Overvoltage category - III
Pollution degree - 3
[Uimp] rated impulse withstand voltage - 6 kV conforming to IEC 60947

Safety reliability level - B10d 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO
13849-1

Mechanical durability - 6 Mcycles
Electrical durability - 1.4 Mcycles 60 A AC-1 at Ue <= 440 V
1.5 Mcycles 40 A AC-3 at Ue <= 440 V
1.5 Mcycles 40 A AC-3e at Ue <= 440 V

Control circuit type - AC at 50/60 Hz standard

Coil technology - Without built-in suppressor module

Control circuit voltage Limits - 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz
0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz
0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz
1...1.1 Uc (60…70 °C):operational AC 50/60 Hz

Inrush Power in VA - 140 VA 60 Hz cos phi 0.75 (at 20 °C)
160 VA 50 Hz cos phi 0.75 (at 20 °C)

Hold-in power consumption in VA - 13 VA 60 Hz cos phi 0.3 (at 20 °C)
15 VA 50 Hz cos phi 0.3 (at 20 °C)

Heat dissipation - 4…5 W at 50/60 Hz

Operating time - 4...19 ms opening
12...26 ms closing

Maximum operating rate - 3600 cyc/h 60 °C
Maximum operating rate - 3600 cyc/h at 60 °C

Permissible ambient air temperature around the device - 40…60 °C/ 60…70 °C with derating
Operating altitude - 0...3000 m
Fire resistance - 850 °C conforming to IEC 60695-2-1
Flame retardance - V1 conforming to UL 94
Mechanical robustness - Vibrations contactor open (2 Gn, 5...300 Hz)
Vibrations contactor closed (4 Gn, 5...300 Hz)
Shocks contactor open (15 Gn for 11 ms)
Shocks contactor closed (10 Gn for 11 ms)

Height - 122 mm
Width - 55 mm
Depth - 120 mm
Net weight - 0.85 kg

Packing Units
Unit Type of Package 1 - PCE
Number of Units in Package 1 - 1
Package 1 Height - 6.3 cm
Package 1 Width - 13.8 cm
Package 1 Length - 15.4 cm
Package 1 Weight - 920.0 g

Unit Type of Package 2 - S02
Number of Units in Package 2 - 10
Package 2 Height - 15.000 cm
Package 2 Width - 30.000 cm
Package 2 Length - 40.000 cm
Package 2 Weight - 9.9 kg

Unit Type of Package 3 - P06
Number of Units in Package 3 160
Package 3 Height 77.0 cm
Package 3 Width 80.0 cm
Package 3 Length 60.0 cm
Package 3 Weight 166.82 kg

18 Months Company Warranty